You are currently browsing the Door Hardware Genius posts tagged: security


Choosing a Delayed Egress System: Self-Contained, or Built from Components?

Delayed egress is a process that delays unauthorized exit from a space while complying with NFPA 101 life safety code.  Use of this process is strictly regulated with the help of building inspectors and fire marshals across the United Sates.  With that in mind it is always a good idea to get your local AHJ (Authority Having Jurisdiction) on board whenever you are planning to install delayed egress on an opening.

When you beginning planning your delayed egress system you will find that many systems on the market are self-contained.    These could be delayed egress electromagnetic locks or electrified delayed egress exit devices.

Here are some examples of self-contained delayed egress maglocks:

  • SDC 1511S
  • Schlage Electronics M490DE
  • Dynalock 3101C

Here are some examples of self-contained delayed egress exit devices:

  • Detex V40 EE
  • Von Duprin Chexit
  • Sargent Electroguard

delayed-egress-anatomy
Almost all delayed egress systems are made up of the same components:

  1. Delayed egress timer and relay logic board
  2. Initiating Switch (to initiate the delayed egress process)
  3. Audible alarm
  4. Signage
  5. Reset switch
  6. Optional bypass switch
  7. Fire Alarm interface
  8. Power supply
  9. Locking device

Therefore it is possible to construct a custom delayed egress system from components.  Later I’ll talk about why you might want to choose a built-from-components delayed egress system instead of a self-contained one.   The following sections describe each part of a built-from-components delayed egress system.

Delayed Egress Timer and Relay Logic Board

This board is UL Listed and specifically designed to perform all delayed egress functions in compliance with life safety code.   Here are some examples of component boards for delayed egress:

  • Securitron XDT-12 or XDT-24
  • Seco-Larm SA-025EQ

The board is the brains of the delayed egress operation.  It has contacts to wire in switches for delayed egress initiation, fire alarm interface and system reset, timers to control nuisance and egress delay, and relays to control locks and notify external devices.

There are also delayed egress controllers that offer more features.  The following may include the delayed egress timer/relay board and some other required feature(s) such as the initiation switch or the audible alarm.

  • Alarm Controls DE-1
  • Security Door Controls 101-DE
  • Securitron BA-XDT-12 or BA-XDT-24

Initiating Switch

The switch that initiates the delayed egress process shares several characteristics with any request-to-exit switch.  To comply with life safety regulations it must require no prior knowledge to operate; it must require no more than one motion to operate; and it must be placed in relation to the door according to life safety standards in your local jurisdiction.  I think that the best possible initiation device is a mechanical push bar with a switch, such as the Adams Rite 8099-M or the Securitron EMB.  In a panic situation it remains obvious that to get out, one must push on the bar, and because it is mechanical it is unaffected by power outage.  If it is wired to open the contact when pushed, if the wires leading to it are cut it will initiate the delayed egress process.

In rare circumstances where it might be permitted, the locking device might be a fail safe electrified mortise lock that is locked on both sides, inside and out.  Then the initiation switch might be a palm switch next to the door.

Audible Alarm

The mandatory audible alarm sounds for 15 seconds before the delayed egress controller releases the locking device to allow exit.  It’s loudness must be between 81 and 88 decibels.  In some jurisdictions the alarm must be manually reset at the door; in others it may be self resetting via timer or door position switch.  Yet another reason to have a heart-to-heart talk with your local AHJ when designing your delayed egress system.

Signage

The wording on the mandatory sign must comply with life safety code.  There are minor variations in wording.  I suggest buying a sign that is part of a delayed egress system.  The sign that comes standard with the Von Duprin Chexit is readily available as a separate part.

Reset Switch

As mentioned in the “Audible Alarm” section above, a delayed egress system reset switch located at the door is mandatory in some jurisdictions.  Check with your local AHJ.  In some jurisdictions delayed egress systems are allowed to be reset by remote switch or other means, such as a door position switch.

Any kind of momentary contact switch will do the reset switch job, but delayed egress system reset switches located at the door almost always require some kind of security to prevent unauthorized resetting.   Standalone keypads or key switches are often used for this purpose.  Delayed egress systems can also be integrated into existing access control.

Optional Bypass Switch

Not required but often needed, the optional bypass switch allows authorized personnel to exit without triggering the delayed egress system.  Again, any momentary contact switch will do, but usually some security is required.  If you are using a keypad as the system reset switch and the keypad has more than one relay, you can program the second relay to be the bypass switch.

If access from the exterior side is required a bypass switch is required on that side.  Sometimes security is not needed from the exterior side.  In that case a simple momentary contact pushbutton will do the job.

Fire Alarm Interface

The mandatory fire alarm interface allows enables fire alarm panel to deactivate the delayed egress system immediately in the event of a fire alarm.  This is an integral part of the life safety code that allows a delayed egress system to exist.  Therefore, if your building does not have a fire alarm panel, without special permission from the local AHJ you cannot have a delayed egress system.

Power Supply

All delayed egress systems I have had experience with run on low voltage power that comes from a low voltage power supply.  Generally delayed egress systems require regulated and filtered power at 12 or 24 volts.  Delayed egress controllers draw very little current, but as will all electrically operated systems, the current draw of all attached devices must be taken into account when selecting a power supply.

Locking Device

The locking device must be electrically locked and fail safe from the egress (interior) side.  The most frequently used locking device in a component based delayed egress system is the electromagnetic lock.

Why Build a Delayed Egress System?

Why would you put together a delayed egress system from components when there are so many good self-contained systems?

  1.  To Save Money.  Piecing together a delayed egress system can be significantly cheaper than buying a self contained delayed egress system.
  2.  To take advantage of existing hardware.  For example, if there is already an electromagnetic lock on the door, adding the other components is relatively easy.
  3. Conditions at the door prohibit use of a self contained delayed egress system.  For example, door size or the presence of existing hardware may require the installer to seek a more creative solution.

 





Bottom line, unless you have a prison, you cannot lock ’em in.  Well, not without permission.  🙂

Securitech Trident Multi-Point Deadbolt Exit Lock

Trident 4-point deadlocking exit device.

Simple and robust design helps to ensure security and longevity; single motion egress ensures life safety code compliance.  

Simple to order and to install, the Trident offers excellent security while preserving life safety.

The first thing I noticed when I unpacked the box was the small number of parts.  The second thing I noticed was how well all of these parts are labelled.  As I read the installation instructions I was struck by how easy Securitech had made the installation process, especially with the inclusion of a metal template to help get everything lined up just right.

I assume that the Trident is named for the three active bolts that secure the door on the lock side, but with the inclusion of the passive hinge side bolt it is actually a four point lock.  The hinge side bolt slides passively into its keeper whenever the door is closed.

Trident is a heavy device, so before installing it, make sure your door swings and closes properly and the hinges are in good shape.  I suggest using hinges with non-removeable pins so as not to rely solely upon the Trident’s hinge side bolt.  A stainless steel continuous hinge would be even better for both security and durability, if it is possible to use one.

Every locking mechanism of the Trident is through-bolted through pry-resistant steel plates, so casual attack using a pry bar would likely be fruitless no matter how much time the would-be burglar might have.  Each locking bolt is substantial and housed in a very sturdy mechanism.  Bending one of them would be difficult; bending all of them enough to gain entry would be almost impossible.  The main outside plate is impressive-looking with its Securitech logo and satin stainless steel finish, and since it is through-bolted to the head of the device in several

Photo by Tom Rubenoff

places, it’s pretty strong, too.

The weakest part of any muli-point locking device is the door frame.  Fully grouted (concrete filled) hollow metal frames hold up the best under attack.  At the very least, to have real security measures must be taken to ensure that the door frame cannot be either pulled out of the wall or bent away from the locking bolts.

To maximize security, I suggest not using the optional exterior key control with this device.  The presence of a key cylinder outside provides a target for burglars.

The Trident comes standard with a paddle that tells the user to push to exit and alarm will sound, but since the alarm is optional, this may be an empty threat.  Be sure to order your Trident with an alarm if you want one.

I was impressed with the workmanship evident in how the Trident is put together.  Everything worked super-smoothly and fit together perfectly.  The strong, simple design looks like it will provide many years of flawless service.  I highly recommend it for the back doors of stores, warehouses or factories or anywhere where a higher level of security may be needed.

Glass Door Electric Locking Solutions

Installing an electric locking system on an existing, currently unsecured all-glass or Herculite door can be a challenge for the security professional, but there are solutions.  Here are a few:

Electromagnetic Locks

Securitron Glass Door Solution

The Securitron solution to the glass door locking problem is… glue.   When I sell this solution, I usually use:

  • M62G (1200 lb. holding force electromagnetic lock with conduit fitting)
  • AKG (adhesive kit for glass doors)
  • GDB (glass door bracket for armature)

For all glass doors with all glass headers, I also use the HEB-G header extension bracket.  This can also be glued in place using the Securitron AKG.  Since the AKG includes enough glue to do 10 glass-door mag installs, there is more than enough to do one all-glass door and one all-glass header.

Everybody Else’s Mag-Lock-for-Glass-Door Solution

As far as I know, no one besides Securitron really deals with the situation of an all glass header.  For all-glass doors, all the other companies that make electromagnetic locks use variations of the HDB, or Herculite Door Bracket.  This bracket is a U-channel that slides down over the top of the door.  It’s a clip-on system:

Illustration from Rutherford Controls web site

The Herculite door bracket concept seems to work well except in cases were there is a reduced gap between the top of the door and the header.  In that case the U-channel idea is out because the HDB bracket will keep the door from closing.  Then it’s the Securitron and the glue or something else altogether.

RCI Cushion-Lok

A pricey but classy and easy to install alternative to the electromagnetic solution is the Rutherford Controls Cushion-Lok.  The Cushion-Lok is a specially constructed, fail safe electric strike and passive latch that gently locks the door upon closure.   Shown below is the RCI 3360 which is pre-installed on patch fittings that slide onto the glass of the door and “frame” when the entire doorway – door, lintels and header – is made of glass.

Not shown is another version for use with a wood or metal frame and Herculite door.

It is worthwhile to note that the reason security professionals are faced with installing electric locks on existing all-glass doors is because of a lack of planning on the part of the architect or project manager.  It is much easier for a glass door manufacturer to pre-install a locking system than it is for a security professional to install it after the fact.


Tags